DRY-WELL FUSEHOLDERS

The Transformers Components dry-well fuseholder provides a method of placing dead front type current limiting fuses within the transformer or other electrical apparatus filled with transformer oil.

Submersible Non-Loadbreak Bolt on Tank

Standard Non-Loadbreak
150 BIL

Standard
Non-Loadbreak

Submersible Non-Loadbreak Weld

Dry-Well Fuseholder for Current Limiting Fuses

The trend towards higher system voltage, increased load density, and larger substations has caused higher fault current potentials on the distribution system and the need to interrupt those higher currents when a fault exists. Current-limiting fusing provides both a high interrupting current rating and limits the peak value of current and the amount of energy to within acceptable levels for protection of the transformer.

 

Improved Design

 

Housing – The  dry-well  housing  consists  of  filament-wound  glass  tubing  with  a  resin-rich  outer. This outer surface serves as the barrier against oil permeation through the tubing wall.  

Dry-well fuseholder location – In Pad Mounted transformer applications, the dry-well fuseholder is mounted on the transformer front plate, below the oil level. Because the current-limiting fuses that these fuse-holders are designed to accept will not function properly if exposed to transformer oil, the interior of the fuseholder must remain oil tight.

 

ECI manufactures two types of dry well fuse holders:

Non-load break for use with both single and three phase padmount applications.
Non-load break for use with both single and three phase submersible applications.

 

Catalog NumberkVBILFuseholder CAPDescription
7559ZC839921.1125 kVPlated SteelTypical non-loadbreak standard construction fuseholder and current limiting fuse assembly. 
7559ZG839921.1125 kVStainless SteelTypical non-loadbreak standard construction fuseholder and current limiting fuse assembly. 
7559ZC849915.2125 kVPlated SteelTypical non-loadbreak standard construction fuseholder and current limiting fuse assembly. 
7559ZG849915.2125 kVStainless SteelTypical non-loadbreak standard construction fuseholder and current limiting fuse assembly. 
7559ZC85998.395 kVPlated SteelTypical non-loadbreak standard construction fuseholder and current limiting fuse assembly. 
7559ZG85998.395 kVStainless SteelTypical non-loadbreak standard construction fuseholder and current limiting fuse assembly. 
Catalog NumberkVBILCapDescription
7559ZC259921.1150 kVPlated SteelTypical non-loadbreak standard construction fuseholder and current limiting fuse assembly. 
Catalog NumberskVBILEnd Cap Stud (0.25-20-2B)Description
7509ZE01998.395 kVNoTypical non-loadbreak submersible construction fuseholder and current limiting fuse assembly. 
7509ZE31998.395 kVYesTypical non-loadbreak submersible construction fuseholder and current limiting fuse assembly.
7509ZE029915.2125 kVNoTypical non-loadbreak submersible construction fuseholder and current limiting fuse assembly.
7509ZE329915.2125 kVYesTypical non-loadbreak submersible construction fuseholder and current limiting fuse assembly.
7509ZE039921.1125 kVNoTypical non-loadbreak submersible construction fuseholder and current limiting fuse assembly.
7509ZE339921.1125 kVYesTypical non-loadbreak submersible construction fuseholder and current limiting fuse assembly.
Catalog NumberkVBILEnd Cap Stud (-.250-20-2B)Description
7559ZE11998.395 kVNoTypical non-loadbreak standard construction fuseholder and current limiting fuse assembly. 
7559ZE21998.395 kVYesTypical non-loadbreak standard construction fuseholder and current limiting fuse assembly.
7559ZE129915.2125 kVNoTypical non-loadbreak standard construction fuseholder and current limiting fuse assembly
7559ZE229915.2125 kVYesTypical non-loadbreak standard construction fuseholder and current limiting fuse assembly.
7559ZE139921.1125 kVNoTypical non-loadbreak standard construction fuseholder and current limiting fuse assembly.
7559ZE239921.1125 kVYesTypical non-loadbreak standard construction fuseholder and current limiting fuse assembly.